S-ASB

ANALOG SOUNDER BASE, BONE COLOR

Product Code:ASB (0300-04330 IT)

The ASB AnalogSounder Base is designed for use with Hochiki analogsensors ALG-V, ALK-V, ACA-V, AIE-EA, and ATG-EA. Each addressable base is to be connected to aHochiki America Corporation DCP Signaling LineCircuit (SLC). The ASB provides an audible alarm in theimmediate vicinity, typical applications arehotels, apartments, and hospitals. Each device has 16 statesthat are programmed with the desired outputpattern to be used (e.g., “Temporal” or “March”)for each state.


STANDARD FEATURES
• Programmable evacuation codes - Continuous, March, ANSI Temporal patterns
• Base learns the sensor address and assumes an upper range address (128-254)
• Up to 127 sensors and 127 ASBs can be used on one SLC loop
• Can be alarmed or reset by zone or by individualaddress
• ASB SLC loop wire resistance = 50 ohms Max.(total SLC wire run length)
• High sound pressure level (85dB SPL at 10 feet)